FOR INTEGRATION WITH SMART HOUSES, SD- AND RESIDENTIAL ALARMS
Art.no 5648412
Remote Interface connects to Smart Stop, Quick Stop and Smart Basic in order to integrate these systems with Smart houses, SD-systems and residential alarms.
APPLICATION AREAS
The system can be used in industrial buildings, private and vacation homes.
PACKAGE CONTENT
Remote Interface | Art.no 5648412 |
ASSEMBLY INSTRUCTIONS
Remote Interface WTG-35A must be connected to the following component:
The control unit WTG-38A, linked with valve controller(s) WTG-36C and wireless sensors WTG-27B.
Pairing:
Remote Interface WTG-35A is paired with the control unit WTG-38A by following this routine:
- Press the button on front until you hear two signals from this unit.
- On the control unit WTG-38A push the reset button until you hear two signals from this unit. The two units will now be paired, followed by a signal when the pairing is complete.
Assembly:
Remote Interface WTG-35A must not be placed inside a closed metal cabinet, nor on a metal surface. This will negatively affect the quality/range of the radio communication with the control unit WTG-38A. WTG-35A must be placed in a dry, open place. Power can be supplied from external units like alarms.
Operation:
Use the push-button located on the front of the unit to open and close the solenoid valve(s) in the system. Green light indicates an open valve and red light indicates a closed valve. The unit has the following connections for wired signals:
Output ports:
For all output ports:
These are intended for signaling Alarm/Smart house/SD systems, not to control loads. Ports are galvanically separated, with max voltage 50V, max current 130mA and max ON resistance 16 ohm, Type 5 ohm.
STATUS ON/OFF
Water OFF: Port is closed
Water ON: Port is open
LEAK ALARM
NC (normally closed) cuts on alarm
TECH ALARM
NC (normally closed) cuts on low battery (ca. 2,2V) in wireless sensors.
Input ports:
Common to both ports:
Controlled by a relay/switch signal on the input port. Alternatively a minus signal can be placed on the respective plus clamp, provided it is the same minus as the voltage supply.